Incident Report from 3 Deaths @ Ice Skating Rink

by on Aug.07, 2018, under News

Fernie 2

On October 16, 2017, the curling brine chiller at the Fernie Memorial Arena was put back into operation after a seasonal shutdown. During the shutdown and seasonal maintenance, ammonia had been detected in the curling brine system, indicating that the curling brine chiller was leaking. At 3:53 a.m. on October 17, 2017, an ammonia alarm in the arena’s mechanical room was triggered and the system was shut down. Between 9:15 a.m. and 9:38 a.m., rising pressure contained within the curling brine system led to the separation of a pipe coupling in the mechanical room. Upon separation of the coupling, an estimated 9 lb. of ammonia was rapidly released into the room followed by additional ammonia from the system. The atmosphere in the mechanical room may have reached or exceeded concentrations of 20,000 parts per million (ppm) of ammonia…  Continuing Reading the report here InvestigationReport-Fernie Accident

fernie 3


Looking for something?

Use the form below to search the site:

Still not finding what you're looking for? Drop a comment on a post or contact us so we can take care of it!